Electric Remote Controlled Fire Monitors
KRF-LSE Electric Remote-Controlled Monitors are suitable to discharge a jet of water or foam solution with a variable discharge pattern from stream up to 120 degrees, creating a wide fog. The KRF-LS is designed for high hazard areas where access for personnel is obstructed and an expansion foam blanket or a cooling water jet is needed.
KRF-LSE Electric Remote-Controlled Monitors are suitable to discharge a jet of water or foam solution with a variable discharge pattern from stream up to 120 degrees, creating a wide fog. The KRF-LS is designed for high hazard areas where access for personnel is obstructed and an expansion foam blanket or a cooling water jet is needed.
KRF-LS is equipped with a local operator control panel and can also be operated manually. Programmable limit switches on each actuator allow a 360º horizontal rotation and vertical travel from -45º to +70º. It is possible to initially set the movement angles of the fire monitor. A modification with explosion-proof actuators and a control panel is available.
THE OVERALL VIEW OF THE KRF-LSE ELECTRIC REMOTE-CONTROLLED MONITOR
Standard characteristics of KORUFIRE Electric Remote-Controlled Monitors
Parameter | Model | |||
S20 | S30 | S40 | S60 | |
Operating pressure range, bar | 0,4 – 1,6 | |||
Rated pressure, bar | 0,8 | |||
Water flow rate* (foam solution) | 15/20/30 | 30/25/35 | 40/35/50 | 60/50/70 |
Reach in meters: | ||||
- Stream** | 58/62/64 | 64/62/72 | 73/72/74 | 76/74/84 |
- Narrow fog** 30° | 36/37/39 | 39/37/42 | 43/42/44 | 46/44/47 |
- Foam stream | 48/50/54 | 54/50/55 | 56/55/61 | 64/61/66 |
Expansion ratio* | 7,0 | |||
Spray jet angle*, deg | 0 - 100 | |||
Monitor movement | ||||
- Horizontal plane, deg. | ±180 (360, not limited) | |||
- Vertical plane, deg. | Up to 90, down to -45 | |||
Monitor traversing speed, deg/s: | ||||
- Without water flow | 12 | |||
-- With water flow | 6 | |||
Monitor’s materials | Materials with mechanical and corrosion-resistant properties meet the operating conditions and requirements for monitors | |||
Notes: *- Values are given at a pressure of 8 bar; **- Jet ranges are given at an angle of inclination of the monitor to the horizon of 30°, set in the working position. |