Electric Remote Controlled Fire Monitors
KRF-LSE Electric Remote-Controlled Monitors are suitable to discharge a jet of water or foam solution with a variable discharge pattern from stream up to 120 degrees, creating a wide fog. The KRF-LS is designed for high hazard areas where access for personnel is obstructed and an expansion foam blanket or a cooling water jet is needed.
KRF-LSE Electric Remote-Controlled Monitors are suitable to discharge a jet of water or foam solution with a variable discharge pattern from stream up to 120 degrees, creating a wide fog. The KRF-LS is designed for high hazard areas where access for personnel is obstructed and an expansion foam blanket or a cooling water jet is needed.
KRF-LS is equipped with a local operator control panel and can also be operated manually. Programmable limit switches on each actuator allow a 360º horizontal rotation and vertical travel from -45º to +70º. It is possible to initially set the movement angles of the fire monitor. A modification with explosion-proof actuators and a control panel is available.
THE OVERALL VIEW OF THE KRF-LSE ELECTRIC REMOTE-CONTROLLED MONITOR


Standard characteristics of KORUFIRE Electric Remote-Controlled Monitors
|
Parameter |
Model |
|||
|
S20 |
S30 |
S40 |
S60 |
|
|
Operating pressure range, bar |
0,4 – 1,6 |
|||
|
Rated pressure, bar |
0,8 |
|||
|
Water flow rate* (foam solution) |
15/20/30 |
30/25/35 |
40/35/50 |
60/50/70 |
|
Reach in meters: |
||||
|
- Stream** |
58/62/64 |
64/62/72 |
73/72/74 |
76/74/84 |
|
- Narrow fog** 30° |
36/37/39 |
39/37/42 |
43/42/44 |
46/44/47 |
|
- Foam stream |
48/50/54 |
54/50/55 |
56/55/61 |
64/61/66 |
|
Expansion ratio* |
7,0 |
|||
|
Spray jet angle*, deg |
0 - 100 |
|||
|
Monitor movement |
||||
|
- Horizontal plane, deg. |
±180 (360, not limited) |
|||
|
- Vertical plane, deg. |
Up to 90, down to -45 |
|||
|
Monitor traversing speed, deg/s: |
||||
|
- Without water flow |
12 |
|||
|
-- With water flow |
6 |
|||
|
Monitor’s materials |
Materials with mechanical and corrosion-resistant properties meet the operating conditions and requirements for monitors |
|||
|
Notes: *- Values are given at a pressure of 8 bar; **- Jet ranges are given at an angle of inclination of the monitor to the horizon of 30°, set in the working position. |
||||