Sushchevsky Val, 5, bld. 2,
Moscow, 127018 Russia
Mon-Fri 10:00-18:00 UTC+3

Electric Remote Controlled Fire Monitors

KRF-LSE Electric Remote-Controlled Monitors are suitable to discharge a jet of water or foam solution with a variable discharge pattern from stream up to 120 degrees, creating a wide fog. The KRF-LS is designed for high hazard areas where access for personnel is obstructed and an expansion foam blanket or a cooling water jet is needed.

KRF-LSE Electric Remote-Controlled Monitors are suitable to discharge a jet of water or foam solution with a variable discharge pattern from stream up to 120 degrees, creating a wide fog. The KRF-LS is designed for high hazard areas where access for personnel is obstructed and an expansion foam blanket or a cooling water jet is needed.

KRF-LS is equipped with a local operator control panel and can also be operated manually. Programmable limit switches on each actuator allow a 360º horizontal rotation and vertical travel from -45º to +70º. It is possible to initially set the movement angles of the fire monitor. A modification with explosion-proof actuators and a control panel is available.

THE OVERALL VIEW OF THE KRF-LSE ELECTRIC REMOTE-CONTROLLED MONITOR

Standard characteristics of KORUFIRE Electric Remote-Controlled Monitors

Parameter

Model

S20
(15,30) U(m)

S30
(25,35) U(m)

S40
(35,50) U(m)

S60
(50,70) U(m)

Operating pressure range, bar

0,4 – 1,6

Rated pressure, bar

0,8

Water flow rate* (foam solution)

15/20/30

30/25/35

40/35/50

60/50/70

Reach in meters:

 

- Stream**

58/62/64

64/62/72

73/72/74

76/74/84

- Narrow fog** 30°

36/37/39

39/37/42

43/42/44

46/44/47

- Foam stream

48/50/54

54/50/55

56/55/61

64/61/66

Expansion ratio*

7,0

Spray jet angle*, deg

0 - 100

Monitor movement

 

- Horizontal plane, deg.

±180 (360, not limited)

- Vertical plane, deg.

Up to 90, down to -45

Monitor traversing speed, deg/s:

 

- Without water flow

12

-- With water flow

6

Monitor’s materials

Materials with mechanical and corrosion-resistant properties meet the operating conditions and requirements for monitors

Notes: *- Values are given at a pressure of 8 bar; **- Jet ranges are given at an angle of inclination of the monitor to the horizon of 30°, set in the working position.